当前位置:首页 >> 产品展示 >> 电工电气 >> 开关 >>NBB8-18GM60-A2-V1-3G-3D 倍加福
NBB8-18GM60-A2-V1-3G-3D 倍加福放大图片

产品价格:面议   元(人民币)
上架日期:2017年4月24日
产地:德国
发货地:上海  (发货期:当天内发货)
供应数量:不限
最少起订:1件
浏览量:23
  暂无相关下载
其他资料下载:

         
上海宽途自动化科技有限公司

点击这里给我发消息
  详细说明  
品牌:倍加福产地:德国
价格:面议人民币/件规格:NBB8-18GM60-A2-V1-3G-3D

简要说明:倍加福牌的NBB8-18GM60-A2-V1-3G-3D 倍加福产品:估价:面议,规格:NBB8-18GM60-A2-V1-3G-3D,产品系列编号:1

详细介绍:

  
General specifications
Switching function complementary
Output type PNP
Rated operating distance 8 mm
Installation flush
Output polarity DC
Assured operating distance 0 ... 6.48 mm
Reduction factor rAl 0.45
Reduction factor rCu 0.4
Reduction factor r304 0.7
Nominal ratings
Operating voltage 10 ... 30 V DC
Switching frequency 0 ... 500 Hz
Hysteresis typ. 5 %
Reverse polarity protection reverse polarity protected
Short-circuit protection pulsing
Voltage drop ≤ 3 V
Operating current 0 ... 200 mA
Off-state current 0 ... 0.5 mA typ. 0.1 μA at 25 °C
No-load supply current ≤ 25 mA
Switching state indicator LED, yellow
Approvals and certificates
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection type Connector M12 x 1 , 4-pin
Housing material brass, nickel-plated
Sensing face PBT
Housing diameter 18 mm
Degree of protection IP67
Equipment protection level Gc (nA)
Certificate of Compliance PF 15CERT3754 X
Special conditions
Protection against transients Ensure transient protection is provided and that the maximum value of the transient protection (140% of 85 V) is not exceeded.
Equipment protection level Dc (tc)
Instruction Manual electrical apparatus for hazardous areas
Device category 3D for use in hazardous areas with combustible dust
Certificate of Compliance PF 15CERT3774 X
CE marking [*PD-Z02586A*]
ATEX marking Ex-Hexagon II 3D Ex tc IIIC T80°C Dc 
The Ex-related marking can also be printed on the enclosed label.
Standards EN 60079-0:2012+A11:2013, EN 60079-31:2014 
Protection by enclosure "tc" Some of the information in this instruction manual is more specific than the information provided in the datasheet.
General The corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents can be found at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet.
Installation, commissioning Laws and/or regulations and standards governing the use or intended usage goal must be observed. If the Ex-relevant identification is printed exclusively on the adhesive label provided, this label must be affixed in the immediate vicinity of the sensor! The background surface to which the adhesivelabel is to be applied must be clean and free from grease! The applied label must be durable and remain legible, with due consideration of the possibility of chemical corrosion!
Maintenance No changes can be made to apparatus, which are operated in hazardous areas.
Repairs to these apparatus are not possible.
Special conditions
Maximum operating current IL The maximum permissible load current must be restricted to the values given in the following list.
High load currents and load short-circuits are not permitted.
Maximum operating voltage UBmax The maximum permissible operating voltage UBmax must be restricted to the values given in the following list. Tolerances are not permitted.
Maximum permissible ambient temperature TUmax dependant of the load current IL and the max. operating voltage UBmax
Information can be taken from the following list.
at UBmax=30 V, IL=200 mA 45 °C (113 °F)
at UBmax=30 V, IL=100 mA 50 °C (122 °F)
at UBmax=30 V, IL=50 mA 50 °C (122 °F)
Protection from mechanical danger The sensor must not be exposed to ANY FORM of mechanical danger.
Protection from UV light The sensor and the connection cable must be protected from damaging UV-radiation. This can be achieved when the sensor is used in internal areas.
Electrostatic charge Electrostatic charges must be avoided on the mechanical housing components. Dangerous electrostatic charges on the mechanical housing components can be avoided by incorporating these in the equipotential bonding. Do not attach the nameplate provided in areas where electrostatic charge can build up.
Plug connector The plug connector must not be withdrawn under voltage. The proximity switch is identified as follows: "WARNING - DO NOT SEPARATE WHEN ENERGIZED". With the plug connector disconnected, soiling of the internal area must be prevented.(i.e. the area that is inaccessible when the connector is inserted)
General information
Use in the hazardous area see instruction manuals
Category 3G; 3D