Model |
HY-P100 |
HY-P101 |
Appearance
DIN(mm) (W)】(H)】(D) |
96】96】160 |
96】96】160 |
Power voltage |
100-240VAC (50/60Hz) |
Power consumption |
Less than 15VA (Except to communication option) |
Input |
Thermo couple, R·T·D, Voltage/Current |
Control output |
Relay contact output: AC250V(Resistive load), SSR: 12VDC(Constant voltage pulse) (load resistance more than 800ヘ), Current: 4mA DC (load resistance less than 500ヘ) |
Control action |
P·I·D (Auto-tuning function), ON/OFF |
Alarm output |
Indipendent Variation Alarm |
Remote |
|
Within Rs-232C |
Setting |
by the Up/Down key |
by the Up/Down or RS-232C |
Display |
L.E.D Display |
Setting and indication accuracy |
【0.3% F·S + 1digit Binput: Within 0…399∩ 【(5% F·S + 1digit) |
Setting resolution |
1 or 0.1 (By input range), Time: 1 minute |
Memory prOtection |
About 10 years |
External control function |
Run, Reset, Pattern NO, Hold |
Instrument accident alarm |
Open Collector Max 24VDC 50mA - OFF (when make an accident) |
Self control function |
RAM check, Data error check, system overcrowding check |
Manual control |
-10…+110(resolution 1%) |
Device control |
Auto-tuning, Alarm setting |
pattern |
6 pattern |
Segment |
16 segment |
Pattern contact |
Until max 6 pattern |
Operation |
999 time or limitless |
program |
Max 1/hour |
Sampling cycle |
500ms |
Reverese/Direct action |
Be selected by inside switch |
Insulation resistance |
More than DC500V 20й(Between terminal and earth), More than DC 1,000V 20й(Between terminal and earth) |
Dielectric strength |
AC 500V for 1 minute (Betweeh terminal and earth) AC 1,000V for 1 minute(Between terminal and earth) |
Ambient temperature and humidity |
0…50∩(32…122⒌)·35…85%RH |