IEC HIGH-SPEED CYLINDRICAL FUSE-LINKS AC PROTECTION
Size 27x60 gRB 800VAC with trip-indicator
Size
voltage AC
(IEC)
Clearing I2t
at
Voltage
breaking
capacity AC
FR27GB80V8T R221436 26x60 800 V 8 A 70 A2s 90 kA 2 W 3/10 80 g
FR27GB80V100T D221447 26x60 800 V 100 A 19000 A2s 90 kA 13 W 3/10 80 g
FR27GB80V110T E221448 26x60 800 V 110 A 27000 A2s 90 kA 14 W 3/10 80 g
FR27GB80V10T S221437 26x60 800 V 10 A 100 A2s 90 kA 2 3 W 3/10 80 g
FR27GB80V12T T221438 26x60 800 V 12 A 180 A2s 90 kA 2 5 W 3/10 80 g
FR27GB80V16T V221439 26x60 800 V 16 A 250 A2s 90 kA 3 5 W 3/10 80 g
FR27GB80V20T W221440 26x60 800 V 20 A 350 A2s 90 kA 4 W 3/10 80 g
FR27GB80V25T X221441 26x60 800 V 25 A 600 A2s 90 kA 5 W 3/10 80 g
FR27GB80V32T Y221442 26x60 800 V 32 A 1000 A2s 90 kA 6 W 3/10 80 g
FR27GB80V40T Z221443 26x60 800 V 40 A 1400 A2s 90 kA 8 W 3/10 80 g
FR27GB80V50T A221444 26x60 800 V 50 A 2700 A2s 90 kA 8 5 W 3/10 80 g
FR27GB80V63T B221445 26x60 800 V 63 A 5500 A2s 90 kA 10 W 3/10 80 g
FR27GB80V80T C221446 26x60 800 V 80 A 11000 A2s 90 kA 11 5 W 3/10 80 g
FR27GB80V110T
Protistor® size 27x60 gR (gRB)
800V
HIGH SPEED FUSES FOR SEMICONDUCTOR PROTECTION
EP MERSEN COM 297
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet
HIGH SPEED
FUSES
LOCK
CMS810PAK
FUSE HOLDERS FOR HIGH-SPEED CYLINDICAL FUSE-LINKS
ACCESSORIES
Modulostar? compact fuse holders for 10 3x38 1 fuse-links, with standard indicator
of poles/
phases
Design Voltage limit for blown fuse
indicator Package
CUS101I J1062723 1 CUS10 single pole - 12
CUS101NI E1062719 1+N CUS10 single pole + neutral conductor - 6
CUS102I F1062720 2 CUS10 double pole - 6
CUS103I B1062716 3 CUS10 triple pole - 4