45DB240V125PTS B1018326 125 A 290 kA2s 65 kA 440 A 10 1 m? 254 W 1 6 1 kg
6 /12 kV, length 442mm
Clearing I2t
at
Voltage
Breaking
capacity I1
Minimum
breaking
current I3
= Imin
Cold resistance
R20
(+/-10%)
Power
dissipation
? 78mm
45DB120V100PTS3 R1018317 100 A 150 kA2s 80 kA 350 A 7 5 m? 95 W 1 5 1 kg
45DB120V125PTS3 S1018318 125 A 300 kA2s 80 kA 440 A 5 4 m? 105 W 1 5 1 kg
45DB120V160PTS3 V1018320 160 A 500 kA2s 80 kA 660 A 4 1 m? 145 W 1 5 1 kg
45DB120V100PTS3
HIGH VOLTAGE FUSE SYSTEM
EP MERSEN COM 252
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet
Limitor®- PD Back-up Fuses
without Controlled , for German standard VDE 0670 T402
Limitor® - PTS Back-up Fuses
with Low and Thermal Striker
DIN HV BACK-UP FUSES FOR TRANSFORMERS
3 / 7,2 kV, length 192mm
current
In
Clearing I2t
at
Voltage
Breaking
capacity I1
Minimum
breaking
current I3 = Imin
Cold resistance
R20 (+/-10%)